Skip to main content
Siemens 3VA2463-5HL32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5HL32-0JA0 SENTRON MCCB, 630 A, 3-Pole, Line

MPN3VA2463-5HL32-0JA0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2463-5HL32-0JA0, 630 A, 3-pole, line protection version with ETU320 electronic trip unit and integrated shunt trip (STL).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5HL32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5HL32-0AA0
3VA2463-5HL32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.162 W
3VA2463-5HL32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2463-5HL32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5HL32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-5HL32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5HL32-0JA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens 3VA2463-5HL32-0JA0 is a SENTRON 3VA2 molded case circuit breaker rated for 630 A continuous current (Iu) in a 3-pole configuration, configured for line protection with an ETU320 electronic overcurrent release and an integrated shunt trip (STL) release. That 630 A rating is at 40 °C ambient; the breaker thermally derates to 520 A at 70 °C, so the actual continuous current your bus can carry depends on enclosure temperature — plan your panel ventilation around the 162 W maximum power loss this unit dissipates at full load. Breaking capacity is 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 17 kA at 690 V — these are the fault currents the breaker can safely interrupt at each voltage level, which governs your SCCR coordination upstream.

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — this is a full-frame 3VA2 breaker sized for 630 A buswork, not a compact frame. Verify your enclosure depth clears 110 mm plus wiring space for the line and load lugs.

Frequently asked questions

Where can I buy 3VA2463-5HL32-0JA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to receive current availability and pricing — no stock or price figures are published here.

What is the breaking capacity of this MCCB at different voltages?

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — these are the maximum fault currents the breaker can safely interrupt at each respective voltage level.

What trip unit does the 3VA2463-5HL32-0JA0 use?

It uses the ETU320 electronic overcurrent release with adjustable protection curves, plus an integrated shunt trip (STL) for remote tripping.

MPN
3VA2463-5HL32-0JA0