The Siemens SENTRON 3VA2463-5HN32-0AA0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU350 electronic trip unit designed for line protection. The 630 A figure is the base rating at 40 °C; above that ambient the breaker derates in steps — 612 A at 45 °C, 593 A at 50 °C, down to 520 A at 70 °C — so the real-world continuous current depends on your enclosure temperature, not just the nameplate number. Breaking capacity is the other headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. At 690 V the 9 kA figure is lower, which is typical for this frame size; if your system runs 690 V with high fault potential, verify coordination with the upstream device. The ETU350 release is an electronic trip unit — adjustable, more precise than thermal-magnetic for coordinating with downstream breakers in a selective scheme. Maximum power loss is 162 W, which matters for heat buildup in a sealed enclosure; factor that into your thermal calculation.

Siemens 3VA2463-5HN32-0AA0 SENTRON MCCB, 630 A, 3-Pole, 187
Siemens SENTRON 3VA2463-5HN32-0AA0, molded case circuit breaker, 3-pole, 630 A continuous rating, ETU350 electronic trip unit, line protection design.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 630 A |
| Current at 45 °C | 612 A |
| Current at 50 °C | 593 A |
| Current at 55 °C | 575 A |
| Current at 60 °C | 557 A |
| Current at 65 °C | 538 A |
| Current at 70 °C | 520 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 9 kA |
| Power loss, max. | 162 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 248 mm |
| Width | 138 mm |
| Depth | 110 mm |
| Height (in) | 9.76 in |
| Width (in) | 5.43 in |
| Depth (in) | 4.33 in |
Product details
Frequently asked questions
What is the breaking capacity of 3VA2463-5HN32-0AA0 at 415 V?
121 kA at 415 V AC. At 240 V it is 187 kA, at 500 V it is 75.6 kA, and at 690 V it is 9 kA.
What does the ETU350 trip unit mean for selectivity?
The ETU350 is an electronic overcurrent release that allows adjustable long-time, short-time, and instantaneous pickup settings. This makes coordination with downstream breakers more precise than a fixed thermal-magnetic release, especially in selective schemes where you need to keep the upstream breaker closed during a downstream fault.
Where can I buy 3VA2463-5HN32-0AA0 and what is the lead time?
This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm delivery commitment.