The Siemens SENTRON 3VA2463-5JP32-0AB0 is a 3-pole molded case circuit breaker rated for continuous current of 630 A at 40 °C, with a thermal derating curve down to 450 A at 70 °C — meaning you size the breaker for the ambient inside the enclosure, not the shop floor. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V — that SCCR headroom covers most industrial fault-current scenarios without cascading upstream. This is a line-protection design with communication function built in, so it can talk to a BMS or PLC for load shedding and trip-event logging.

Siemens SENTRON 3VA2463-5JP32-0AB0 MCCB, 630A, 187kA at 240V
MPN3VA2463-5JP32-0AB0
Siemens SENTRON 3VA2463-5JP32-0AB0, molded case circuit breaker, 3-pole, 630 A rated, 187 kA at 240 V, line protection, with communication function.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA2463-5JP32-0AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA11 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 630 A |
| Current at 45 °C | 600 A |
| Current at 50 °C | 570 A |
| Current at 55 °C | 540 A |
| Current at 60 °C | 510 A |
| Current at 65 °C | 480 A |
| Current at 70 °C | 450 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 75.6 kA |
| Breaking capacity at 690 V | 9 kA |
| Power loss, max. | 162 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU550 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | Yes |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 248 mm |
| Width | 138 mm |
| Depth | 110 mm |
| Height (in) | 9.76 in |
| Width (in) | 5.43 in |
| Depth (in) | 4.33 in |
Product details
Frequently asked questions
Will 3VA2463-5JP32-0AB0 drop into a panel specified for 3VA2116-5JP32-0AE0?
Both are SENTRON 3VA frame sizes with the same mounting footprint, so the mechanical fit is the same — no rewiring of the backplate needed. The electrical ratings differ, so verify the load current and SCCR against the panel design.
MPN
3VA2463-5JP32-0AB0