Skip to main content
Siemens 3VA2463-5JP42-0KB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5JP42-0KB0 Circuit Breaker, 630A, 55kA @ 415

MPN3VA2463-5JP42-0KB0

Siemens 3VA2 IEC frame 630, breaking capacity class M, Icu=55kA @ 415V, 4-pole, ETU550 LSI, In=630A, shunt trip left, 2 auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA2463-5JP42-0KB0 is a 4-pole IEC frame 630 circuit breaker from the 3VA2 series, rated for line protection with an ETU550 trip unit offering LSI (long-time, short-time, instantaneous) protection. The 630 A frame covers feeder and large motor circuits; the ETU550 allows adjustable overload protection Ir from 250 A to 630 A and short-circuit pickup Isd from 0.6 to 9x In, so it fits a range of downstream loads without changing the breaker frame.

For most industrial 400 V distribution, this covers high-capacity transformer secondaries and large motor control centers where fault levels run 50 kA or higher. The built-in shunt trip (left side, 208-277 V AC 50/60 Hz, 220-250 V DC) allows remote emergency-off or undervoltage release without an external shunt trip module.

Panel Integration

Mounts in a standard IEC 60947-2 compliant panel — DIN-rail or screw-mount depending on the 3VA2 base plate. The 4-pole form factor (3 phases + neutral) with adjustable N-conductor protection (OFF to 100%) suits 3-phase 4-wire systems where the neutral must be protected or left unprotected. The nut keeper kit (included) prevents terminal hardware from loosening under vibration in transport or high-fault installations. Verify the shunt trip coil voltage matches the control circuit before wiring; the left-side shunt trip occupies the accessory slot closest to the line terminals.

Frequently asked questions

Where can I buy 3VA2463-5JP42-0KB0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of this breaker?

The ultimate breaking capacity Icu is 55 kA at 415 V AC, class M per IEC 60947-2.

What trip unit does 3VA2463-5JP42-0KB0 use?

It uses an ETU550 LSI trip unit with adjustable overload protection Ir from 250 A to 630 A, short-time pickup Isd from 0.6 to 9x In, and instantaneous pickup Ii from 1.5 to 9x In.

MPN
3VA2463-5JP42-0KB0