Skip to main content
Siemens 3VA2463-5JQ32-0HL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5JQ32-0HL0 SENTRON MCCB, 630 A, 187 kA at 24

MPN3VA2463-5JQ32-0HL0

Siemens SENTRON 3VA2463-5JQ32-0HL0, molded case circuit breaker, 3-pole, 630 A, 187 kA at 240 V, ETU560 electronic trip unit, line protection version with shunt trip and communication.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5JQ32-0HL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2463-5JQ32-0HL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.162 W
3VA2463-5JQ32-0HL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2463-5JQ32-0HL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5JQ32-0HL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2463-5JQ32-0HL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5JQ32-0HL0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The Siemens 3VA2463-5JQ32-0HL0 is a SENTRON 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU560 electronic trip unit for line protection. Breaking capacity reaches 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — meaning this breaker handles high fault currents at common distribution voltages without cascading upstream. Current derating is specified across the operating temperature range: 630 A at 40 °C, stepping down to 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C — critical for panel builders sizing the breaker in a warm enclosure.

Auxiliaries and releases

Communication function is integrated, and the overcurrent release is the ETU560 electronic unit with a voltage trigger for alarm outputs.

Frequently asked questions

What auxiliary contacts are fitted on this breaker?

It carries two auxiliary switches, one trip alarm switch, and one electrical alarm switch — the HQ auxiliary contact version, plus a shunt trip release (STL).

MPN
3VA2463-5JQ32-0HL0