Skip to main content
Siemens 3VA2463-5KP32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5KP32-0AG0 SENTRON MCCB, 630 A, 187 kA

MPN3VA2463-5KP32-0AG0

Siemens SENTRON 3VA2463-5KP32-0AG0, 3-pole molded case circuit breaker, 630 A rated continuous current Iu, 187 kA interrupting at 240 V, ETU850 electronic trip unit, communication function, 138 mm wide × 248 mm high × 110 mm deep.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5KP32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2463-5KP32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.162 W
3VA2463-5KP32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2463-5KP32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5KP32-0AG0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2
3VA2463-5KP32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5KP32-0AG0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. If this breaker lands in a hot switchroom or a non-climate-controlled enclosure, the 70 °C figure (450 A) is the one that governs the load it can actually carry — not the 630 A nameplate.

Communication and auxiliary contact configuration

This MCCB includes a communication function, which on the 3VA platform typically means it can interface with a fieldbus or Ethernet gateway for power monitoring and remote trip indication — useful for a plant-wide energy management system or a PLC-driven shutdown sequence. The auxiliary contact version is specified as 1 auxiliary switch + 1 trip alarm switch HP, giving one N.O./N.C. set for status and a separate alarm contact that changes state only on a trip event, not on manual open. The basic switch (the breaker mechanism without the trip unit) is order code 3VA2463-5KP32-0AA0, and the integrated auxiliary trip is 3VA9608-0BB11 — these are the spare-part codes if the ETU850 or the auxiliary switch needs replacement separately.

Where this MCCB fits in the system

A 630 A MCCB with 187 kA interrupting capacity and electronic trip is typically the main breaker in a 240 V or 415 V distribution panel feeding downstream subpanels, motor control centers, or large single loads (chillers, compressors, large pumps). The ETU850 supports adjustable long-time pickup and delay, short-time pickup and delay, instantaneous pickup, and ground-fault — so it can be coordinated with downstream breakers and fused switches.

Frequently asked questions

Where can I buy 3VA2463-5KP32-0AG0 and get a price?

This part is sourced and quoted to order through independent industrial distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not from a live stock counter.

What are the key interrupting ratings for 3VA2463-5KP32-0AG0?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. The 187 kA figure at 240 V is the highest and governs its use on high-capacity transformer secondaries.

What is the depth of 3VA2463-5KP32-0AG0?

110 mm depth, with a width of 138 mm and height of 248 mm. These dimensions are for the breaker body without protruding handle or auxiliary modules.

Will 3VA2463-5KP32-0AG0 drop into a panel specified around 5SQ2370-2YA05?

Not without verification. The 3VA2 series has a different mounting footprint and bus-bar spacing than the older 5SQ series. Measure the panel cutout against the 138 mm × 248 mm × 110 mm envelope before ordering.

MPN
3VA2463-5KP32-0AG0