Skip to main content
Siemens 3VA2463-5KP32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5KP32-0AH0 SENTRON MCCB, 630 A, 3-Pole

MPN3VA2463-5KP32-0AH0

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2463-5KP32-0AH0, 3-pole, 630 A at 40 °C, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5KP32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2463-5KP32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-5KP32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-5KP32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5KP32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts3
3VA2463-5KP32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5KP32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

630 A MCCB with onboard communication

The Siemens 3VA2463-5KP32-0AH0 is a SENTRON 3VA2 molded case circuit breaker rated for 630 A continuous at 40 °C, with a maximum breaking capacity of 187 kA at 240 V.

Breaking capacity scales with system voltage: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. This covers most low-voltage distribution networks from 240 V single-phase through 690 V three-phase.

Thermal derating curve

Continuous current rating derates with ambient temperature: 630 A at 40 °C, 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. For a panel running at 50 °C ambient, plan for 570 A continuous — roughly 10% below the 40 °C nameplate.

The 138 mm width fits standard 3-pole MCCB mounting footprints in distribution boards. Maximum power dissipation is 162 W — factor this into enclosure thermal calculations to avoid derating the breaker by its own heat.

Frequently asked questions

What are the key ratings for this MCCB?

Continuous current is 630 A at 40 °C, with breaking capacity of 187 kA at 240 V and 121 kA at 415 V. It is a 3-pole unit with onboard communication function.

Where can I buy 3VA2463-5KP32-0AH0?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current availability and pricing.

What is the physical size of this breaker?

Dimensions are 248 mm high, 138 mm wide, and 110 mm deep — a standard 3-pole MCCB footprint.

Does this MCCB include communication capability?

Yes, the 3VA2463-5KP32-0AH0 has a communication function onboard for integration with monitoring and control systems.

MPN
3VA2463-5KP32-0AH0