Skip to main content
Siemens 3VA2463-5KP32-0AJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5KP32-0AJ0 SENTRON MCCB, 630 A, 3-pole, ETU8

MPN3VA2463-5KP32-0AJ0

Siemens SENTRON 3VA2463-5KP32-0AJ0, molded case circuit breaker, 3-pole, 630 A, ETU850 electronic trip unit, line protection, 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5KP32-0AJ0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB11
3VA2463-5KP32-0AJ0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V17 kA
Power loss, max.162 W
3VA2463-5KP32-0AJ0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2463-5KP32-0AJ0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5KP32-0AJ0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts3
3VA2463-5KP32-0AJ0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5KP32-0AJ0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

The 3VA2463-5KP32-0AJ0 is a 3-pole SENTRON molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU850 electronic trip unit. That 630 A figure is the maximum uninterrupted current the breaker can carry under standard conditions; at elevated panel temperatures the rating derates linearly — 600 A at 45 °C, 570 A at 50 °C, and down to 450 A at 70 °C. For a panel builder, the derating curve matters more than the headline number: if your enclosure runs at 55 °C, the usable rating is 540 A, not 630 A. The interrupting capacity is equally load-dependent: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. The ETU850 is a fully electronic, communication-capable trip unit. It supports the Communication Function and Other Measurement Function, meaning it can report current values and trip events over a bus — useful for a plant-wide power monitoring scheme.

Panel integration — dimensions and mounting

The breaker measures 138 mm wide, 248 mm high, and 110 mm deep. The maximum power loss is 162 W, so factor that into your thermal budget if the breaker is enclosed without forced ventilation.

As a Siemens SENTRON product, the 3VA2463-5KP32-0AJ0 carries the usual IEC/UL certifications for molded case circuit breakers. The manufacturer provides RoHS and REACH declarations, plus IEC 60947-2 test reports. For an emergency breakdown contractor or a panel builder needing compliance paperwork, these documents are available from Siemens directly or through the distributor at quote time.

Frequently asked questions

How do I get current pricing and availability for 3VA2463-5KP32-0AJ0?

Pricing and stock levels are confirmed at quote time. Submit an RFQ through this listing; the distributor will return current availability and a firm price for your quantity and delivery location.

What is 3VA2463-5KP32-0AJ0's listed depth (110 mm) on this component line?

The depth is 110 mm, which is the dimension from the mounting surface to the farthest projection of the breaker body. This is shallow enough for most 200 mm deep enclosures.

What is 3VA2463-5KP32-0AJ0's listed width (138 mm) on this component line?

The width is 138 mm, matching the standard 3-pole SENTRON 3VA2 frame footprint. It fits the same panel cutout as other breakers in the 3VA2 family.

What compliance documentation does this brand provide for 3VA2463-5KP32-0AJ0 (RoHS, REACH, UL, IEC)?

Siemens provides RoHS and REACH declarations, plus IEC 60947-2 test reports for this SENTRON MCCB. UL certification is also standard for the series. Request the specific documents with your RFQ.

MPN
3VA2463-5KP32-0AJ0