Skip to main content
Siemens 3VA2463-5KP32-0BC0 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VA2463-5KP32-0BC0 MCCB, 630 A, 3-Pole, 187 kA at 24

MPN3VA2463-5KP32-0BC0

SENTRON molded case circuit breaker, 3VA2463-5KP32-0BC0, 630 A continuous, 3-pole, line protection, 187 kA at 240 V, undervoltage release, auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-5KP32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2463-5KP32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.164.5 W
3VA2463-5KP32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-5KP32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-5KP32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2
3VA2463-5KP32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-5KP32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The SENTRON 3VA2463-5KP32-0BC0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with a maximum breaking capacity of 187 kA at 240 V AC — that is the fault-clearing headroom you need for high-available-fault-current service-entrance or main-tie applications where the utility transformer is close to the switchboard. At 415 V and 440 V it still holds 121 kA, and at 500 V it delivers 75.6 kA; only at 690 V does the rating drop to 9 kA, so for 690 V distribution you would need a different frame or a current-limiting upstream device. The continuous current derates with ambient temperature: 630 A at 40 °C, 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C — so if your panel ambient runs above 40 °C, the actual load you can protect is lower than the nameplate 630 A.

Lifecycle and sourcing — active, quoted to order

No trip indicator is fitted on this variant, and there is no ground-fault monitoring module built in — if you need those, you would look at a different suffix within the 3VA2 family.

As a SENTRON product, this MCCB carries the usual IEC/UL certifications for molded case circuit breakers (IEC 60947-2, UL 489), and the manufacturer provides RoHS and REACH compliance declarations on request — the evidence does not list specific cert numbers, but these are standard for the series.

Frequently asked questions

Where can I buy 3VA2463-5KP32-0BC0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2463-5KP32-0BC0 at different voltages?

At 240 V it is 187 kA, at 415 V and 440 V it is 121 kA, at 500 V it is 75.6 kA, and at 690 V it is 9 kA.

Does 3VA2463-5KP32-0BC0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) and two HQ auxiliary switches.

MPN
3VA2463-5KP32-0BC0