Skip to main content
Siemens 3VA2463-5KP32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5KP32-0BH0 SENTRON MCCB, 630 A, 3-Pole, 187

MPN3VA2463-5KP32-0BH0

Siemens SENTRON 3VA2463-5KP32-0BH0, molded case circuit breaker, 3-pole, 630 A continuous at 40 °C, 187 kA breaking capacity at 240 V, line protection design with communication function and undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-5KP32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2463-5KP32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.164.5 W

Protection & Trip Unit

3VA2463-5KP32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2463-5KP32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-5KP32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2463-5KP32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-5KP32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

630 A MCCB for line protection with communication and UVR

The Siemens SENTRON 3VA2463-5KP32-0BH0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, designed for line protection in industrial distribution panels. Its 187 kA breaking capacity at 240 V handles high-fault scenarios without cascading upstream — critical for selectivity studies on large switchboards. The breaker includes an undervoltage release (UVR) and a communication function, making it suitable for monitored power distribution where remote trip indication or load shedding is required.

Breaking capacity across voltage levels

Rated short-circuit breaking capacity varies by system voltage: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 9 kA at 690 V. This voltage-dependent curve means the breaker's interrupting rating is not a single number — verify the available fault current at your specific line-to-line voltage. At 690 V the 9 kA figure limits application to lower-fault industrial networks or transformer-secondary positions.

Thermal derating and ambient temperature

Continuous current rating derates with rising ambient temperature inside the enclosure: 630 A at 40 °C, 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. If the panel ambient runs above 40 °C, size the breaker for the derated value — the 630 A frame may need a lower trip unit setting to avoid nuisance tripping in a hot switchroom. Operating range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Auxiliary switches and release configuration

Factory-fitted with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), and an undervoltage release (UVR). The UVR trips the breaker when control voltage drops below a threshold — used for emergency stop circuits or undervoltage protection on motor feeders. The trip indicator confirms the breaker opened on fault vs. manual switching. No ground-fault monitoring version is included on this variant.

Physical dimensions and panel fit

Dimensions: 248 mm height, 138 mm width, 110 mm depth. The 3-pole frame fits standard MCCB mounting patterns in distribution panels. Depth of 110 mm is moderate — verify clearance for rear-connected busbars or cable terminations, especially in shallow enclosures.

Frequently asked questions

What is the breaking capacity of 3VA2463-5KP32-0BH0 at 415 V?

121 kA at 415 V, matching the rating at 440 V. At 240 V it reaches 187 kA; at 500 V it drops to 75.6 kA; at 690 V it is 9 kA.

Where can I buy 3VA2463-5KP32-0BH0 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

Does 3VA2463-5KP32-0BH0 include an undervoltage release?

Yes, it is factory-equipped with an undervoltage release (UVR) plus 2 auxiliary switches and 1 trip alarm switch.

What is the continuous current rating at 50 °C ambient?

570 A at 50 °C, derated from the 630 A rating at 40 °C. The full derating curve covers 40 °C through 70 °C.

MPN
3VA2463-5KP32-0BH0