Skip to main content
Siemens 3VA2463-5KP32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-5KP32-0HC0 SENTRON MCCB, 630 A, 187 kA

MPN3VA2463-5KP32-0HC0

Siemens SENTRON 3VA2463-5KP32-0HC0, molded case circuit breaker, 3-pole, 630 A at 40 °C, 187 kA at 240 V, line protection with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-5KP32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2463-5KP32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-5KP32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2463-5KP32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-5KP32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2463-5KP32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-5KP32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this MCCB delivers — and where the ratings matter

The Siemens SENTRON 3VA2463-5KP32-0HC0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with a maximum breaking capacity of 187 kA at 240 V. That 187 kA figure drops to 121 kA at 415 V and 440 V, then to 75.6 kA at 500 V, and further to 9 kA at 690 V — the SCCR headroom you need for high-fault installations like transformer secondaries or large motor control centers. The continuous current derates predictably with ambient temperature: 600 A at 45 °C, 570 A at 50 °C, down to 450 A at 70 °C. If your panel ambient runs above 40 °C, size the breaker against the derated value, not the 630 A nameplate. The unit includes a shunt trip (STL) release and two auxiliary switches (HQ) for remote status feedback. It also carries a communication function via the SENTRON communication module.

Panel fit and mounting

The breaker measures 248 mm high, 138 mm wide, and 110 mm deep. The 138 mm width is the standard 3-pole MCCB footprint for this SENTRON frame size.

Frequently asked questions

Does this breaker include a shunt trip or undervoltage release?

It includes a shunt trip (STL) release and two auxiliary switches (HQ). No undervoltage release or ground-fault monitoring is fitted on this variant.

MPN
3VA2463-5KP32-0HC0