Skip to main content
Siemens 3VA2463-6HL32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6HL32-0CH0 SENTRON MCCB, 630 A, 3-Pole

MPN3VA2463-6HL32-0CH0

Siemens SENTRON 3VA2463-6HL32-0CH0, molded case circuit breaker, 3-pole, 630 A, line protection, 242 kA interrupting at 240 V, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-6HL32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA2463-6HL32-0CH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V9 kA
Power loss, max.164.5 W
3VA2463-6HL32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-6HL32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-6HL32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2463-6HL32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-6HL32-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

630 A MCCB for main feeder protection

The 110 mm depth and 138 mm width fit standard panel-mount cutouts; the 248 mm height leaves room for busbar connections above and below.

This breaker is rated 630 A at 40 °C ambient, but the continuous current drops as the panel warms: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C.

Interrupting ratings across voltages

The 3VA2463-6HL32-0CH0 delivers 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V.

Built-in auxiliary and release options

Communication function is not included — this is a standalone thermal-magnetic or electronic-trip breaker, not a networked power meter.

Frequently asked questions

What are the key ratings for this MCCB?

630 A continuous at 40 °C, 3-pole, interrupting capacity of 242 kA at 240 V and 187 kA at 415 V. Includes undervoltage release and 2 auxiliary switches plus trip alarm.

Where can I buy 3VA2463-6HL32-0CH0?

Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time.

What are the physical dimensions of this breaker?

Depth 110 mm, width 138 mm, height 248 mm — fits standard panel cutouts for 630 A frame MCCBs.

Does this breaker include an undervoltage release?

Yes, it is factory-fitted with an undervoltage release (UVR) plus 2 auxiliary switches and 1 trip alarm switch.

MPN