Skip to main content
Siemens 3VA2463-6HN32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6HN32-0AB0 SENTRON MCCB, 630 A, 242 kA

MPN3VA2463-6HN32-0AB0

Siemens SENTRON 3VA2463-6HN32-0AB0, molded case circuit breaker, 3-pole, 630 A at 40 °C, interrupting 242 kA at 240 V, ETU350 trip unit, depth 110 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-6HN32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-6HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2463-6HN32-0AB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-6HN32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350

Construction & Connection

3VA2463-6HN32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-6HN32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2463-6HN32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-6HN32-0AB0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this 3VA2463-6HN32-0AB0 brings to the panel

The Siemens SENTRON 3VA2463-6HN32-0AB0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an interrupting capacity of 242 kA at 240 V. That interrupting rating means it can safely clear a fault up to that level without the arc flashing over or the breaker failing — critical for high-fault-current panels near transformers or large motor banks. The ETU350 electronic trip unit gives you adjustable long-time, short-time, and instantaneous protection curves, so you can shape the trip response to the load instead of living with a fixed thermal-magnetic curve.

Physical fit and panel integration

The case measures 248 mm high, 138 mm wide, and 110 mm deep. That 110 mm depth is a key number for shallow enclosures or gland-plate clearance — it's shallower than many MCCBs in this current class, so it fits where a deeper breaker would hit the back wall. The front face carries IP40 protection, meaning it's sealed against tools and wires over 1 mm but not against water spray; keep it inside a rated enclosure.

Derating and ambient temperature

The 630 A rating holds only at 40 °C ambient. As the panel warms up, the breaker derates: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. If your panel runs hot — say, a packed MCC lineup near a furnace line — you need to size up or accept the lower continuous current. The maximum operating temperature is 70 °C; storage range is -40 °C to 80 °C.

Auxiliary contacts and accessories

This variant comes with two auxiliary switches (high-performance type) built in — handy for status feedback to a PLC or for interlocking without adding a separate contact block. There is no undervoltage release, no shunt trip, no ground-fault monitoring, and no voltage trip on this order code. If you need those, you'd look at a different suffix. The power loss at full load is 162 W, so factor that into your enclosure thermal budget.

Frequently asked questions

What is the interrupting capacity of 3VA2463-6HN32-0AB0 at different voltages?

The interrupting capacity varies with voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. Use the rating that matches your system voltage — the 240 V figure is the highest, but at 690 V it drops to 40 kA.

How do I get current pricing and availability for 3VA2463-6HN32-0AB0?

Submit an RFQ through this listing. We source this breaker through independent distribution and confirm current pricing and availability at quote time — no automated stock numbers here.

What is 3VA2463-6HN32-0AB0's listed depth?

The depth is 110 mm. That's a key dimension for shallow enclosures — it's shallower than many 630 A MCCBs, so it fits where a deeper breaker would hit the back wall.

What trip unit does 3VA2463-6HN32-0AB0 use?

It uses the ETU350 electronic trip unit, which provides adjustable long-time, short-time, and instantaneous protection curves. That gives you flexibility to match the breaker to motor or feeder loads without swapping trip units.

MPN
3VA2463-6HN32-0AB0