Siemens 3VA2463-6HN42-0KJ0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6HN42-0KJ0 630A 85kA @ 415V 4-Pole Breaker

MPN3VA2463-6HN42-0KJ0

Siemens 3VA2 series, circuit breaker, IEC frame 630, breaking capacity class H, Icu=85kA @ 415V, 4-pole, line protection ETU350 LSI, In=630A, overload protection Ir=250A...630A, short-circuit protection Isd=1.5...9x Ir, Ii=9x In, N conductor protection adjustable (OFF, 50%, 100%), nut keeper kit, shunt trip left 208-277 V AC 50/60 Hz 220-250 V DC, 2 auxiliary switch channels.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

The Siemens 3VA2463-6HN42-0KJ0 is a 4-pole IEC frame 630 circuit breaker with a class H breaking capacity of 85kA at 415V. It carries an ETU350 LSI trip unit, adjustable overload protection from 250A to 630A, and short-circuit protection set at 1.5 to 9 times Ir with an instantaneous pickup of 9x In. The neutral conductor protection can be set to OFF, 50%, or 100% of phase protection. A factory-fitted shunt trip (left side, 208-277V AC / 220-250V DC) and two auxiliary switch channels are included, plus a nut keeper kit for secure mounting.

What the ratings mean for fit

The 85kA Icu at 415V class H rating means this breaker can safely interrupt fault currents up to that level on a 415V system without failing catastrophically — critical for high-fault-capacity industrial feeds like transformer secondaries or large motor control centers. The ETU350 LSI trip unit provides electronic long-time, short-time, and instantaneous protection, giving you selectivity coordination with downstream devices. The adjustable N protection (OFF, 50%, 100%) lets you match the breaker to a 4-wire system where neutral loading varies.

Panel integration

The 3VA2 frame mounts onto a DIN rail or panel-mount adapter in standard switchgear enclosures. The shunt trip and auxiliary switches are pre-installed on the left side, so verify clearance for wiring access and any right-side accessories you may add later. The nut keeper kit simplifies torque-down on the main lugs — no loose washers to drop into a live panel.

Frequently asked questions

What is the breaking capacity of this breaker?

The 3VA2463-6HN42-0KJ0 has a class H breaking capacity with Icu=85kA at 415V, suitable for high-fault-current industrial applications.

What accessories are included with this breaker?

It comes with a factory-fitted shunt trip (left side, 208-277V AC / 220-250V DC), two auxiliary switch channels, and a nut keeper kit for the main lugs.

Where can I buy 3VA2463-6HN42-0KJ0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.