Siemens 3VA2463-6JP32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2463-6JP32-0HC0 MCCB, 630 A, 3-Pole, 242

MPN3VA2463-6JP32-0HC0

Siemens SENTRON molded case circuit breaker, 3VA2463-6JP32-0HC0, 630 A continuous, 3-pole, line protection design, breaking capacity 242 kA at 240 V, 187 kA at 415 V, with communication function and shunt trip.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-6JP32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2463-6JP32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-6JP32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-6JP32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-6JP32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2463-6JP32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-6JP32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Its interrupting capacity reaches 242 kA at 240 V and 187 kA at 415 V, falling to 9 kA at 690 V — the high 240 V figure means this breaker handles the available fault current on the secondary side of a typical 480 V–240 V step-down transformer without cascading upstream. Thermal derating is published across the ambient range: 630 A at 40 °C, 570 A at 50 °C, 510 A at 60 °C, and 450 A at 70 °C, so the continuous current you can actually pass depends on the panel internal temperature, not just the nameplate. Adjustable short-time pickup spans 945 A to 5 670 A. The base switch is order code 3VA2463-6JP32-0AA0, meaning this -0HC0 variant adds the communication and auxiliary-switch package on top of the same interruptor core.

MPN
3VA2463-6JP32-0HC0