Interrupting capacity and thermal derating — the real fit numbers
Interrupting capacity is voltage-dependent: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V. The continuous current rating of 630 A is at 40 °C; derate linearly to 450 A at 70 °C. For a panel running at 50 °C ambient, the usable current drops to 570 A.
The shunt trip release allows remote tripping from a control system or emergency-stop circuit.