Skip to main content
Siemens 3VA2463-6JP32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6JP32-0KC0 SENTRON MCCB, 630 A, 242 kA at 24

MPN3VA2463-6JP32-0KC0

Siemens SENTRON 3VA2463-6JP32-0KC0, molded case circuit breaker, 3-pole, 630 A, line protection version with ETU550 electronic trip unit, 242 kA at 240 V, communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-6JP32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-6JP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2463-6JP32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.162 W
3VA2463-6JP32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
3VA2463-6JP32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-6JP32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2463-6JP32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-6JP32-0KC0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

That 630 A figure is the thermal benchmark — derate to 600 A at 45 °C, 570 A at 50 °C, and so on down to 450 A at 70 °C (–). For a 480 V panel running near 600 A, this breaker holds without nuisance tripping, but if your ambient inside the enclosure hits 50 °C, you're sizing at 570 A, not 630 A. Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V (–). That means you can coordinate selectively with downstream breakers and still get fast clearing on a hard fault. The communication function lets the breaker talk to a monitoring system, so you're not walking the panel to read the trip flag.

Mounting and integration — footprint and auxiliaries

Dimensions are 248 mm height, 138 mm width, 110 mm depth. The 138 mm width is a standard 3-pole MCCB footprint for this class — it fits the same cutout as other SENTRON 3VA frames, so a panel laid out for a 630 A 3VA will accept this unit without re-drilling the mounting plate. The auxiliary contacts report breaker position back to the PLC or status light — useful for a remote open/closed indication without adding a separate limit switch. The shunt trip lets a safety relay or E-stop drop the breaker remotely. Maximum power loss is 162 W. That's the heat the breaker dumps into the enclosure at full rated current.

Lifecycle and sourcing — current production, quoted to order

That covers most indoor and outdoor enclosure installations in temperate and cold climates.

Frequently asked questions

Where can I buy 3VA2463-6JP32-0KC0 and how is it quoted?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quote — no stock figures or price lists are published here.

What is the breaking capacity of 3VA2463-6JP32-0KC0 at 480 V?

At 440 V the breaking capacity is 187 kA, and at 500 V it is 121 kA. For a 480 V system, use the 440 V figure (187 kA) as the conservative coordination value since 480 V falls between those two test points.

What trip unit does this MCCB use?

It uses the ETU550 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves. It is not a fixed thermal-magnetic unit.

Does 3VA2463-6JP32-0KC0 support communication?

Yes, it has a communication function, allowing integration with monitoring systems for remote status and trip data.

MPN
3VA2463-6JP32-0KC0