Skip to main content
Siemens 3VA2463-6JQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6JQ32-0AA0 SENTRON MCCB, 630 A, 3-Pole

MPN3VA2463-6JQ32-0AA0
Active

Siemens SENTRON 3VA2463-6JQ32-0AA0, molded case circuit breaker, 3-pole, 630 A, line protection, 242 kA at 240 V, 187 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-6JQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2463-6JQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-6JQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2463-6JQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-6JQ32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-6JQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-6JQ32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

630 A MCCB with voltage-graded interrupting ratings

Its interrupting capacity scales with system voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 9 kA at 690 V — the 690 V figure is the one to watch if you're feeding a 600 V class motor drive center, because that's where the fault current capability drops sharply.

Temperature derating and power loss

Above that, the breaker derates linearly: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. If your panel ambient runs 50 °C, you lose 60 A of headroom — size the upstream feeder accordingly. Maximum power loss is 162 W at rated load, which factors into enclosure heat dissipation calculations.

Dimensions: 248 mm high, 138 mm wide, 110 mm deep. 138 mm width fits standard 3-pole MCCB footprint.

Ground-fault and communication capability

Ground-fault monitoring via summation current formation on line conductor. Communication function included. No undervoltage release, voltage trigger, or trip indicator.

MPN
3VA2463-6JQ32-0AA0