Skip to main content
Siemens 3VA2463-6JQ32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6JQ32-0HH0 SENTRON MCCB, 630 A, 3-pole

MPN3VA2463-6JQ32-0HH0

Siemens SENTRON 3VA2463-6JQ32-0HH0, molded case circuit breaker, 3-pole, 630 A rated current, ETU560 electronic trip unit, line protection, 242 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-6JQ32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-6JQ32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2463-6JQ32-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-6JQ32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2463-6JQ32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-6JQ32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2463-6JQ32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-6JQ32-0HH0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

What this MCCB carries — and what that means for the panel

The Siemens SENTRON 3VA2463-6JQ32-0HH0 is a 3-pole molded case circuit breaker rated for continuous current Iu of 630 A at 40 °C, with an insulation voltage Ui of 800 V. That 630 A figure is the thermal backbone — it governs the main bus connection and sets the upper bound for the downstream load schedule. The ETU560 electronic trip unit gives you adjustable overload and short-circuit protection curves, plus a communication function for status feedback over the network. Breaking capacity runs from 242 kA at 240 V down to 40 kA at 690 V, so the SCCR headroom is substantial for most industrial distribution panels.

Selectivity and thermal derating — the real coordination numbers

The 630 A rating holds only at 40 °C ambient. Above that, the continuous current derates linearly: 600 A at 45 °C, 570 A at 50 °C, 540 A at 55 °C, 510 A at 60 °C, 480 A at 65 °C, and 450 A at 70 °C. If the panel ambient runs at 50 °C, this MCCB effectively becomes a 570 A device — that matters when you're coordinating with an upstream feeder breaker or sizing the busbar. Maximum power loss is 162 W, so ventilation inside the enclosure isn't optional; it's a thermal budget line item.

What the auxiliary contacts and releases tell you

The breaker ships with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration) — that's enough for remote status indication on a PLC digital input card without adding external interface relays. The shunt trip release (STL) is built in, so a remote emergency-stop signal or undervoltage protection scheme can trip the breaker directly. Ground fault monitoring uses summation current formation on the L-conductor, which means it detects residual current without a separate core-balance CT — saves panel space and wiring. The trip indicator and voltage trigger are both present, so a local flag confirms the breaker opened on fault, not manual operation.

Physical fit and environmental limits

Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard 3-pole MCCB footprint for 630 A frame size. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C. The 15 000 mechanical endurance cycles (latching) is typical for a 630 A electronic-trip MCCB — it's not a switching device for frequent motor starts, but it handles routine isolation and fault interruption without issue.

Frequently asked questions

Where can I buy 3VA2463-6JQ32-0HH0?

This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time commitment.

What is the breaking capacity of 3VA2463-6JQ32-0HH0 at different voltages?

Breaking capacity is 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. That covers most industrial distribution fault-current scenarios.

What trip unit does 3VA2463-6JQ32-0HH0 use?

It uses the ETU560 electronic trip unit, which provides adjustable overload and short-circuit protection curves with communication capability.

Does 3VA2463-6JQ32-0HH0 include ground fault monitoring?

Yes, it includes ground fault monitoring via summation current formation on the L-conductor, detecting residual current without a separate core-balance CT.

MPN
3VA2463-6JQ32-0HH0