Skip to main content
Siemens 3VA2463-6JQ32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6JQ32-0KA0 SENTRON MCCB, 630 A, 242 kA at 24

MPN3VA2463-6JQ32-0KA0

Siemens SENTRON, 3VA2463-6JQ32-0KA0, 3-pole molded case circuit breaker, 630 A rated continuous current, ETU560 electronic trip unit, breaking capacity 242 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-6JQ32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2463-6JQ32-0AA0
3VA2463-6JQ32-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V40 kA
Power loss, max.162 W
3VA2463-6JQ32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
3VA2463-6JQ32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-6JQ32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-6JQ32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-6JQ32-0KA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm

Product details

For a body-shop weld line where fault current can spike fast, the ETU560 lets you coordinate selectivity downstream without nuisance tripping that kills takt time. Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and still 40 kA at 690 V. That covers most industrial distribution panels feeding motor control centers or large drives. Current derating is published across the operating temperature range: 630 A at 40 °C, stepping down to 450 A at 70 °C.

Integration — what fits inside the can

The integrated auxiliary trip is order code 3VA9688-0BL33. No auxiliary contact block is included — order separately if you need status feedback to a PLC. Communication function is present on this variant, which means it can talk to a higher-level system for power monitoring or remote trip indication. No undervoltage release, no phase-failure detection, no trip indicator flag on the front.

MPN
3VA2463-6JQ32-0KA0