630 A MCCB with the breaking capacity to match
The breaker carries a full thermal derating curve: 630 A at 40 °C, stepping down to 450 A at 70 °C. Power loss is 164.5 W maximum at rated load. That matters for enclosure thermal calculations: a 630 A frame dumping 164.5 W needs ventilation or a larger cabinet to stay below the 70 °C operating ceiling.
The UVR drops the breaker when control voltage falls below the dropout threshold — standard for emergency-stop or undervoltage protection schemes. The trip alarm switch signals a fault condition separately from the aux position, which simplifies PLC-based fault logging.