Siemens 3VA2463-6KP42-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-6KP42-0BC0 Circuit Breaker, 630A, 85kA @ 415

MPN3VA2463-6KP42-0BC0

Siemens 3VA2 IEC frame 630, breaking capacity class H, Icu=85kA @ 415V, 4-pole, line protection ETU850, LSI, In=630A, overload protection Ir=250A...630A, short-circuit protection Isd=0.6..9x In, Ii=1.5..9x In, N conductor protection adjustable (OFF, up to 100%), nut keeper kit, undervoltage release (UVR) 24V DC, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

The Siemens 3VA2463-6KP42-0BC0 is a 4-pole IEC frame 630 molded case circuit breaker with class H interrupting capacity — 85 kA at 415 V AC. That rating means it clears high-fault currents on the main distribution board without cascading upstream, so you can hold selectivity on a 415 V bus with a transformer-fed switchboard. The ETU850 electronic trip unit gives you LSI protection: long-time (Ir) adjustable 250 A to 630 A, short-time (Isd) 0.6 to 9× In, and instantaneous (Ii) 1.5 to 9× In. Neutral protection is adjustable from OFF up to 100% of the phase setting — useful on a 4-wire system where you need to coordinate the neutral with the phase conductors. The UVR drops the breaker on loss of control voltage — standard for emergency-stop chains or undervoltage protection schemes.

The 3VA2 platform is Siemens' main IEC MCCB family for commercial and industrial distribution.

For a 480 V system, check the derated Icu; the IEC frame 630 is typically rated at 480 V as well, but the exact figure depends on the specific UL or IEC listing. The adjustable LSI curve and neutral protection make this breaker suitable for main or tie applications on a 4-wire, 3-phase distribution panel where you need to protect the neutral conductor against overload from harmonic currents. The UVR at 24 V DC integrates with a safety PLC or emergency-stop relay that drops the main breaker on a trip condition.

Frequently asked questions

What is the breaking capacity of this breaker?

Breaking capacity class H with Icu = 85 kA at 415 V AC, 4-pole configuration.

What trip unit and protection functions does it have?

ETU850 electronic trip unit with LSI protection: long-time Ir adjustable 250 A to 630 A, short-time Isd 0.6 to 9× In, instantaneous Ii 1.5 to 9× In. Neutral protection adjustable from OFF to 100%.

What accessories are included with this order code?

Includes a nut keeper kit, undervoltage release (UVR) 24 V DC, and two HQ auxiliary switches.

Where can I buy the 3VA2463-6KP42-0BC0 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.