The Siemens SENTRON 3VA2463-7HL32-0BC0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an interrupting capacity of 330 kA at 240 V and 242 kA at 415 V.
Thermal derating — the real-world current you can count on
At 50 °C the continuous current drops to 593 A; at 60 °C it's 557 A; at 70 °C it's 520 A. That derating curve is the figure to use for the BOM, not the catalogue maximum.
The breaker measures 110 mm deep, 138 mm wide, and 248 mm tall. The 3-pole footprint and the auxiliary switch slot (2 HQ switches included) mean it fits into existing SENTRON panel layouts without re-drilling the gland plate.