It carries a breaking capacity of 330 kA at 240 V, 242 kA at 415 V, and 52.5 kA at 690 V — figures that govern its ability to interrupt fault currents without upstream cascade.
Above that, the continuous current must be derated: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. Maximum power loss is 162 W. These limits define the enclosure ventilation and grouping constraints for a panel designer.
Physical integration and auxiliary wiring
No communication function or undervoltage release is fitted.