Skip to main content
Siemens 3VA2463-7HN32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-7HN32-0AC0 SENTRON MCCB, 630 A, 3-pole

MPN3VA2463-7HN32-0AC0

Siemens SENTRON 3VA2463-7HN32-0AC0, molded case circuit breaker, 3-pole, 630 A rated continuous current, line protection design, 330 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-7HN32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-7HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2463-7HN32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-7HN32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2463-7HN32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-7HN32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2463-7HN32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-7HN32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What the ratings mean for fit

The 3VA2463-7HN32-0AC0 is a Siemens SENTRON molded case circuit breaker (MCCB) rated for 630 A continuous current at 40 °C — that is the thermal benchmark for sizing in a closed panel. Above 40 °C the breaker derates linearly: 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. If your panel ambient runs 50 °C, the usable current is 593 A, not the nameplate 630 A. The interrupting ratings span 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V — the 690 V figure drops sharply because arc extinction physics changes at that voltage. This is a line-protection design (not motor-protection), so it is intended for feeder and distribution duty, not direct motor starting. The failure mode to watch is thermal accumulation at the terminals under sustained high load. With a maximum power loss of 162 W, the breaker dissipates heat into the enclosure. If the panel is tightly packed with other heat sources, that 162 W shifts the internal ambient upward, which eats into the derating headroom. Plan the gland plate and ventilation accordingly — the 110 mm depth, 138 mm width, and 248 mm height give you the envelope for DIN-rail or screw-mount integration.

Lifecycle and sourcing reality

The basic switch variant is listed as 3VA2463-7HN32-0AA0 — the -0AC0 suffix indicates the auxiliary switch configuration: two auxiliary switches (HQ type) are fitted. No undervoltage release, no ground-fault monitoring, no communication function are included. If your spec requires those, this is the clean base variant.

Mounting and integration

Three-pole design, 110 mm deep × 138 mm wide × 248 mm tall. The width is the critical panel cutout dimension — 138 mm is standard for a 630 A frame MCCB in the SENTRON 3VA series. Verify the DIN-rail or screw-mount pattern against your existing backplate; the 3VA2463 frame shares the same footprint as other 630 A SENTRON breakers, so a panel cut for a 3VA2163-8HM32-0AA0 will accept this unit without rewiring.

Frequently asked questions

Where can I buy 3VA2463-7HN32-0AC0 and what is the lead time?

This part is quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

Will 3VA2463-7HN32-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0?

No — the 3VA1110-5ED36-0AC0 is a different frame size and current rating. The 3VA2463 is a 630 A frame (138 mm wide, 248 mm tall, 110 mm deep), while the 3VA1110 is a smaller frame. A panel cut for the 3VA1110 cannot accept the 3VA2463 without enclosure modification.

What are the interrupting ratings for 3VA2463-7HN32-0AC0?

330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 9 kA at 690 V. The steep drop at 690 V is characteristic of air-break MCCBs at that voltage.

MPN