Skip to main content
Siemens 3VA2463-7HN32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-7HN32-0DC0 SENTRON MCCB, 630 A, 3-Pole, 330

MPN3VA2463-7HN32-0DC0

Siemens SENTRON molded case circuit breaker, 3VA2463-7HN32-0DC0, 3-pole, 630 A continuous (40 °C), 330 kA breaking at 240 V, line protection with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-7HN32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-7HN32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2463-7HN32-0DC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.164.5 W

Protection & Trip Unit

3VA2463-7HN32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2463-7HN32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-7HN32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2463-7HN32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-7HN32-0DC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

What this 630 A MCCB carries

The Siemens SENTRON 3VA2463-7HN32-0DC0 is a 3-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with a maximum breaking capacity of 330 kA at 240 V AC. That 330 kA figure drops to 242 kA at 415/440 V and 187 kA at 500 V, so the available fault current at the panel location determines which voltage column you use for coordination. It includes an undervoltage release (UVR) and two auxiliary switches HQ as shipped. Thermal derating is published across the range: 630 A at 40 °C, 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, 520 A at 70 °C. If your panel ambient runs above 40 °C, size the breaker one frame up or accept the lower continuous rating.

Panel fit and dimensions

The breaker measures 138 mm wide, 248 mm high, 110 mm deep. That 138 mm width is the standard 3-pole SENTRON 3VA frame footprint; it drops into the same mounting cutout and bus-bar pattern as other 3VA2-frame breakers. The undervoltage release and auxiliary switches are factory-installed — no field-add kit to track down.

Frequently asked questions

Where can I buy 3VA2463-7HN32-0DC0 and get a price?

This part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the depth of 3VA2463-7HN32-0DC0?

The depth is 110 mm (4.33 in).

What is the width of 3VA2463-7HN32-0DC0?

The width is 138 mm (5.43 in).

MPN