Skip to main content
Siemens 3VA2463-7HN32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-7HN32-0JA0 SENTRON MCCB, 630 A, 3-Pole, 330

MPN3VA2463-7HN32-0JA0

Siemens SENTRON 3VA2463-7HN32-0JA0, molded case circuit breaker, 3-pole, 630 A at 40 °C, 330 kA breaking at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-7HN32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA2463-7HN32-0AA0
3VA2463-7HN32-0JA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W
3VA2463-7HN32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-7HN32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-7HN32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-7HN32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-7HN32-0JA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2463-7HN32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 630 A continuous current at 40 °C, with a maximum breaking capacity of 330 kA at 240 VAC. This is a line-protection device, meaning it is designed for main feeder or large distribution applications where high fault current capability is required to maintain selectivity downstream.

Thermal derating and power dissipation

This matters for panel layout — if the breaker is enclosed with other heat sources, the actual ampacity may be lower than the nameplate. Maximum power loss is 162 W, which must be considered in the enclosure thermal budget.

Integrated shunt trip release

The undervoltage release is not fitted on this order code. If undervoltage protection is required, specify a different variant or add an external relay.

Dimensions are 248 mm height, 138 mm width, 110 mm depth. The width is the critical dimension for multi-pole grouping in a panel — three poles fit in a 138 mm wide footprint.

Frequently asked questions

What is the maximum power loss of this breaker?

The maximum power loss is 162 W. This figure must be included in the enclosure thermal calculation to avoid exceeding the 70 °C maximum operating temperature.

MPN
3VA2463-7HN32-0JA0