Skip to main content
Siemens 3VA2463-7JQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA2463-7JQ42-0AA0 SENTRON MCCB, 630 A, 4-Pole, ETU560, 330

MPN3VA2463-7JQ42-0AA0
Active

SENTRON 3VA series, molded case circuit breaker, 3VA2463-7JQ42-0AA0, 4-pole, 630 A at 40 °C, ETU560 electronic trip unit, line protection version, breaking capacity 330 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-7JQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2463-7JQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C630 A
Current at 45 °C600 A
Current at 50 °C570 A
Current at 55 °C540 A
Current at 60 °C510 A
Current at 65 °C480 A
Current at 70 °C450 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V9 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-7JQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560

Construction & Connection

3VA2463-7JQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-7JQ42-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2463-7JQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-7JQ42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.8 in
Width (in)7.2 in
Depth (in)4.3 in

Product details

The SENTRON 3VA2463-7JQ42-0AA0 is a 4-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU560 electronic trip unit configured for line protection. Its interrupting capacity hits 330 kA at 240 V and 242 kA at 415 V — numbers that place it squarely in high-fault-duty main-breaker territory for industrial switchboards and transformer secondaries.

What the ratings mean for the panel

The 630 A frame at 40 °C is the base rating. Derate linearly as the cabinet ambient climbs: 600 A at 45 °C, 570 A at 50 °C, all the way to 450 A at 70 °C. If your switchgear is in a non-conditioned space or packed with heat-producing gear, size the load to the derated figure — the 630 A number only holds at 40 °C ambient. Breaking capacity of 330 kA at 240 V and 242 kA at 415 V means this breaker can safely interrupt faults up to those levels without cascading upstream — critical for a main or tie position where available fault current is high. At 690 V the rating drops to 9 kA, so confirm system voltage before committing the BOM line. The ETU560 electronic trip unit provides adjustable long-time pickup and delay (tr from 0.5 s to 12 s), plus ground-fault monitoring via summation current on L+N. The N-conductor protection is adjustable OFF or 20% to 100% of the phase setting — useful for sizing the neutral on non-linear loads.

Panel integration notes

The breaker occupies 248 mm height, 184 mm width, and 110 mm depth — a 4-pole frame sized for standard switchboard mounting. Front protection is IP40, adequate for indoor panel environments. The communication function supports integration with monitoring systems, though the protocol is not specified in the listing; verify compatibility with your BMS or SCADA gateway.

Frequently asked questions

What is the breaking capacity of 3VA2463-7JQ42-0AA0 at 415 V?

242 kA at 415 V, which covers most industrial low-voltage switchgear applications with high available fault current.

What electronic trip unit does this MCCB use?

The ETU560 electronic trip unit, with adjustable long-time pickup and delay settings (tr 0.5 s to 12 s) and ground-fault monitoring via summation current on L+N.

Where can I buy 3VA2463-7JQ42-0AA0?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

MPN
3VA2463-7JQ42-0AA0