Skip to main content
Siemens 3VA2463-8HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-8HL42-0AA0 SENTRON MCCB, 630 A, 4-Pole, ETU3

MPN3VA2463-8HL42-0AA0
Active

Siemens SENTRON 3VA2463-8HL42-0AA0, molded case circuit breaker, 4-pole, 630 A continuous current at 40 °C, ETU320 electronic trip unit, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2463-8HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2463-8HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.162 W

Protection & Trip Unit

3VA2463-8HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2463-8HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2463-8HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2463-8HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2463-8HL42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

What the ratings mean for your panel

The Siemens SENTRON 3VA2463-8HL42-0AA0 is a 4-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU320 electronic trip unit designed for line protection. The 630 A frame size means it handles the full load of a large distribution feeder or a heavy industrial load center without needing external current transformers up to that point. The ETU320 provides adjustable overload and short-circuit protection curves, so you set the trip thresholds to match your downstream cable and load — not a fixed thermal-magnetic characteristic. Breaking capacity is the real differentiator here: 440 kA at 240 V AC and 330 kA at 415 V AC. That puts this breaker in the high-interrupting category — it clears a bolted fault on a large transformer secondary or a capacitor bank without the arc re-striking. At 690 V it still holds 52.5 kA, which covers most 690 V industrial distribution systems in mining or marine applications. The 800 V rated insulation voltage (Ui) confirms the internal clearances are sized for 690 V line-to-line systems with margin. Thermal derating is published across the operating range: 630 A at 40 °C, 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. If your enclosure ambient runs at 50 °C, you must size the downstream load to 593 A or less — the breaker itself does not trip, but the internal temperature rise at full rating exceeds the design margin. The maximum power loss of 162 W at rated current is the heat you need to vent through the enclosure.

Panel integration and mounting

Dimensions: 248 mm height, 184 mm width, 110 mm depth. The 4-pole frame at 184 mm wide occupies 7.24 inches of panel-mount width. IP40 on the front face. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. The -25 °C lower limit means it can sit in an unheated electrical room in cold climates, but the breaker mechanism may need to be exercised before closing at extreme low end. No undervoltage release and no communication function on this variant — it is a standalone line-protection breaker without remote trip or monitoring.

Frequently asked questions

What trip unit does the 3VA2463-8HL42-0AA0 use?

The ETU320 electronic trip unit, providing adjustable overload and short-circuit protection for line protection applications.

MPN
3VA2463-8HL42-0AA0