Siemens 3VA2463-8HL42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2463-8HL42-0AA0 SENTRON MCCB, 630 A, 4-Pole, ETU3

MPN3VA2463-8HL42-0AA0
Active

Siemens SENTRON 3VA2463-8HL42-0AA0, molded case circuit breaker, 4-pole, 630 A continuous current at 40 °C, ETU320 electronic trip unit, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2463-8HL42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2463-8HL42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C612 A
Current at 50 °C593 A
Current at 55 °C575 A
Current at 60 °C557 A
Current at 65 °C538 A
Current at 70 °C520 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.162 W
3VA2463-8HL42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2463-8HL42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2463-8HL42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2463-8HL42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2463-8HL42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

The Siemens SENTRON 3VA2463-8HL42-0AA0 is a 4-pole molded case circuit breaker rated for 630 A continuous current at 40 °C, with an ETU320 electronic trip unit designed for line protection. The 630 A frame size means it handles the full load of a large distribution feeder or a heavy industrial load center without needing external current transformers up to that point. That puts this breaker in the high-interrupting category — it clears a bolted fault on a large transformer secondary or a capacitor bank without the arc re-striking. Thermal derating is published across the operating range: 630 A at 40 °C, 612 A at 45 °C, 593 A at 50 °C, 575 A at 55 °C, 557 A at 60 °C, 538 A at 65 °C, and 520 A at 70 °C. If your enclosure ambient runs at 50 °C, you must size the downstream load to 593 A or less — the breaker itself does not trip, but the internal temperature rise at full rating exceeds the design margin.

Dimensions: 248 mm height, 184 mm width, 110 mm depth. The 4-pole frame at 184 mm wide occupies 7.24 inches of panel-mount width. IP40 on the front face.

Frequently asked questions

What trip unit does the 3VA2463-8HL42-0AA0 use?

The ETU320 electronic trip unit, providing adjustable overload and short-circuit protection for line protection applications.

MPN