Skip to main content
Siemens 3VA2510-5HL32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HL32-0AC0 SENTRON MCCB, 1000 A, 3-Pole, ETU

MPN3VA2510-5HL32-0AC0

Siemens SENTRON 3VA2 series, molded case circuit breaker, 3-pole, 1000 A rated continuous current Iu, ETU320 LI electronic overcurrent release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HL32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HL32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HL32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
3VA2510-5HL32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HL32-0AC0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HL32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HL32-0AC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

It is fitted with an ETU320 electronic overcurrent release configured for LI protection — meaning it provides long-time delay (L) and instantaneous (I) fault response, with no ground-fault monitoring. This is the part you spec for a main feeder or large subfeed in a 400 V to 690 V distribution panel where you need adjustable pickup and time bands to coordinate with downstream breakers. The breaking capacity is substantial: 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V.

At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A.

Trip unit adjustability

The ETU320 release gives you an adjustable long-time pickup (Ir) from 1000 A minimum, and instantaneous pickup (Ii) adjustable from 1500 A to 10 000 A. The long-time delay tr is settable between 0.5 and 17 seconds. That range lets you shape the trip curve to ride through motor-start inrush or transformer magnetizing current while still clearing a bolted fault fast.

Dimensions are 210 mm wide × 320 mm high × 120 mm deep.

MPN
3VA2510-5HL32-0AC0