Skip to main content
Siemens 3VA2510-5HL32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HL32-0AF0 SENTRON MCCB, 1000 A, 3-Pole, ETU

MPN3VA2510-5HL32-0AF0

Siemens SENTRON 3VA2510-5HL32-0AF0, molded case circuit breaker, 3-pole, 1000 A, ETU320 electronic trip unit, line protection, breaking capacities 187 kA at 240 V / 121 kA at 415 V / 53 kA at 690 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HL32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HL32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HL32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2510-5HL32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HL32-0AF0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HL32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HL32-0AF0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that give you headroom for high-fault utility feeds or transformer secondaries without cascading upstream.

Trip unit and selectivity

The ETU320 is an electronic release with adjustable long-time pickup (Ir) from 400 A to 1000 A and short-time pickup (Ii) from 1500 A to 10 000 A, plus adjustable long-time delay (tr) from 0.5 s to 17 s. That range lets you coordinate downstream feeders without nuisance trips on motor inrush or capacitor banks — common pain point on fixed-trip breakers.

Physical integration

Dimensions: 320 mm high, 210 mm wide, 120 mm deep. The 3-pole footprint matches standard SENTRON 3VA mounting rails; no special adapter needed for retrofit into existing 3VA or earlier 3VL cutouts.

Frequently asked questions

What is the breaking capacity of 3VA2510-5HL32-0AF0 at 415 V?

121 kA at 415 V, which covers most industrial secondary-side fault levels without needing a current-limiting upstream breaker.

Where can I buy 3VA2510-5HL32-0AF0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA2510-5HL32-0AF0 drop into a panel specified around 5SQ2370-2YA05?

The 3VA2510-5HL32-0AF0 is a SENTRON 3VA frame MCCB; the 5SQ2370-2YA05 is a different series. Physical dimensions and mounting pattern differ — a direct drop-in without rewiring or drilling new mounting holes is not guaranteed. Verify the cutout and bus bar spacing against the 320 x 210 x 120 mm envelope before ordering.

MPN
3VA2510-5HL32-0AF0