Skip to main content
Siemens 3VA2510-5HL32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HL32-0BL0 MCCB, 1000 A, 3-Pole, ETU320

MPN3VA2510-5HL32-0BL0

Siemens SENTRON 3VA2510-5HL32-0BL0, molded case circuit breaker, 3-pole, 1000 A, ETU320 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HL32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HL32-0BL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HL32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2510-5HL32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HL32-0BL0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HL32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HL32-0BL0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2510-5HL32-0BL0 is a SENTRON molded case circuit breaker (MCCB) rated for 1000 A continuous current at 40 °C, with a 3-pole configuration and an ETU320 electronic trip unit. It's a line-protection version — meaning it's designed for feeder and main breaker duty, not motor protection. The interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V, so it handles high-fault scenarios on the secondary side of a distribution transformer or at the main switchboard.

Thermal derating and trip unit

At 60 °C it drops to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. The ETU320 release gives you adjustable long-time pickup (Ir) from 400 A to 1000 A and short-time/instantaneous pickup (Ii) from 1500 A to 10000 A, with time delays tr from 0.5 s to 17 s. That's enough flexibility to coordinate with downstream feeders without a separate relay.

Dimensions are 210 mm wide, 320 mm tall, and 120 mm deep — that's 8.3 in by 12.6 in by 4.7 in. It's a three-pole frame, so it occupies one standard MCCB mounting position in a switchboard or panel.

Frequently asked questions

Where can I buy 3VA2510-5HL32-0BL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will 3VA2510-5HL32-0BL0 drop into a panel that was specified around 5SQ2370-2YA05 without rewiring?

The 3VA series shares the same mounting footprint and lug centers as the 5SQ2370 frame, so power connections should fit without rewiring. Verify the ETU320's auxiliary power wiring against the existing control circuit before committing.

What is 3VA2510-5HL32-0BL0's interrupting capacity at 415 V?

It's rated 121 kA at 415 V, which covers most industrial secondary-side fault levels.

MPN
3VA2510-5HL32-0BL0