Siemens 3VA2510-5HL32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HL32-0CH0 SENTRON MCCB, 1000 A, 187 kA at 2

MPN3VA2510-5HL32-0CH0

Siemens SENTRON 3VA2510-5HL32-0CH0, 3-pole molded case circuit breaker, line protection version, rated continuous current 1000 A, interrupting rating 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HL32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HL32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HL32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2510-5HL32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HL32-0CH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HL32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HL32-0CH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens SENTRON 3VA2510-5HL32-0CH0 is a 3-pole molded case circuit breaker (MCCB) in the line protection version, rated for a continuous current Iu of 1000 A at 40 °C through 55 °C, with a slight derating to 955 A at 60 °C and 815 A at 70 °C. Its interrupting ratings are 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that tell you this breaker is sized for high-fault-capacity main or feeder protection in a 480 V or 690 V industrial distribution panel, not for branch circuit duty.

Above 55 °C the thermal curve drops — at 70 °C you lose nearly 20 % of the rating. The ETU320 electronic trip unit gives adjustable long-time pickup Ir from 400 A to 1000 A and short-time pickup Ii from 1500 A to 10 000 A, with adjustable time delays tr from 0.5 s to 17 s. That range lets you coordinate selectively with downstream breakers on a motor control center or lighting panel.