Skip to main content
Siemens 3VA2510-5HL42-0KF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HL42-0KF0 SENTRON MCCB, 1000 A, 4-Pole, ETU

MPN3VA2510-5HL42-0KF0

Siemens SENTRON 3VA2510-5HL42-0KF0, molded case circuit breaker, 4-pole, 1000 A rated continuous current, ETU320 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HL42-0KF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HL42-0KF0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HL42-0KF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2510-5HL42-0KF0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HL42-0KF0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HL42-0KF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HL42-0KF0 — Mechanical
ParameterValue
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11 in

Product details

The Siemens SENTRON 3VA2510-5HL42-0KF0 is a 4-pole molded case circuit breaker rated for 1000 A continuous current at 40 °C through 55 °C, with a slight derating curve starting at 60 °C (955 A) down to 815 A at 70 °C. That flat thermal plateau up to 55 °C gives you headroom in a warm enclosure without oversizing the frame. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — figures that place it in the high-interrupting range for industrial distribution where fault currents can exceed 100 kA. The ETU320 electronic trip unit gives you adjustable long-time pickup (Ir) from 400 A to 1000 A and instantaneous pickup (Ii) from 1500 A to 10000 A, plus adjustable N-conductor protection (OFF, 50%, 100%).

Dimensions are 280 mm wide, 320 mm high, 120 mm deep.

Frequently asked questions

Where can I buy 3VA2510-5HL42-0KF0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

What is 3VA2510-5HL42-0KF0's listed depth (120 mm) on this component line?

The depth is 120 mm, with a width of 280 mm and height of 320 mm.

What compliance documentation does this brand provide for 3VA2510-5HL42-0KF0?

As a Siemens SENTRON product, it carries the standard industrial approvals expected for an MCCB of this class. Specific certification marks (UL, CSA, CE, IEC) should be verified against the nameplate and manufacturer documentation at time of order.

MPN
3VA2510-5HL42-0KF0