Skip to main content
Siemens 3VA2510-5HN32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HN32-0AE0 SENTRON MCCB, 1000 A, ETU350, 3-P

MPN3VA2510-5HN32-0AE0

Siemens SENTRON 3VA2510-5HN32-0AE0, molded case circuit breaker, 3-pole, line protection, 1000 A rated continuous current, ETU350 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HN32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HN32-0AE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HN32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2510-5HN32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HN32-0AE0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HN32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HN32-0AE0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2510-5HN32-0AE0 is a SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 1000 A at 40 °C through 55 °C without derating — it holds full-rated current across the typical panel ambient range, only starting to taper above 60 °C (955 A at 60 °C, 815 A at 70 °C). That means for most installations inside a ventilated enclosure, you don't have to oversize the frame for ambient heat. Three-pole construction with an ETU350 electronic trip unit gives you adjustable long-time pickup (Ir) from 0.5 to 1.0 × In — so you can dial the 1000 A frame down to 500 A if the load doesn't need the full rating — plus short-time delay (tsd) adjustable from 0.04 s to 0.4 s and instantaneous pickup (Ii) up to 10 000 A. That selectivity window lets you coordinate downstream feeders without sacrificing fault clearance speed.

Interrupting capacity across voltage levels

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — high enough to handle most utility transformer secondary faults without needing a current-limiting fuse upstream. The 121 kA figure at 415 V is what you'd check first for a 400 V distribution panel in a plant main switchboard; it gives you headroom above typical available fault currents in industrial settings.

Dimensions are 210 mm wide × 320 mm high × 120 mm deep — a standard 3-pole MCCB footprint for the 1000 A frame class. The 120 mm depth is what matters for shallow backpanel enclosures; it clears most 200 mm deep cabinets without interfering with the gland plate or door swing. Rated IP40 on the front face, so it's fine for indoor switchgear but needs a secondary cover or higher-rated enclosure if washdown or dust is present.

Frequently asked questions

Where can I buy 3VA2510-5HN32-0AE0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — no stock count or price is published here.

What is the interrupting capacity of 3VA2510-5HN32-0AE0 at 415 V?

At 415 V the interrupting capacity is 121 kA. For reference, it also carries 187 kA at 240 V and 53 kA at 690 V.

What is the depth of 3VA2510-5HN32-0AE0?

The depth is listed as 120 mm. Overall dimensions are 210 mm wide × 320 mm high × 120 mm deep.

Will 3VA2510-5HN32-0AE0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

The 5SQ2370-2YA05 is a different manufacturer's MCCB in the same general class. While both are 3-pole molded case breakers, the exact mounting pattern, bus-bar spacing, and terminal arrangement differ — you would need to verify physical interchangeability against the existing panel layout and bus connections before assuming a direct drop-in.

MPN
3VA2510-5HN32-0AE0