Skip to main content
Siemens 3VA2510-5HN32-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HN32-0JH0 SENTRON MCCB, 1000 A, 187 kA at 2

MPN3VA2510-5HN32-0JH0

Siemens SENTRON 3VA2510-5HN32-0JH0, Molded case circuit breaker, 3-pole, 1000 A, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V, ETU350 release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5HN32-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5HN32-0JH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5HN32-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2510-5HN32-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5HN32-0JH0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-5HN32-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5HN32-0JH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

Siemens SENTRON 3VA2510-5HN32-0JH0 — 1000 A MCCB with ETU350 Release

Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that tell you this breaker is sized for high-fault main feeders or large distribution panels where SCCR headroom is the deciding spec, not the load current alone. The ETU350 electronic trip unit gives you adjustable long-time pickup (Ir) from 0.5 to 1.0 × Iu, short-time delay (tsd) from 0.04 to 0.4 s, and instantaneous pickup (Ii) up to 10 000 A. That adjustability means you can shape the trip curve to coordinate with downstream breakers — essential for selectivity in a multi-level distribution panel.

At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. Physical footprint: 320 mm high, 210 mm wide, 120 mm deep. That's a 3-pole frame that fits standard MCCB mounting patterns in switchboards and panelboards.

Frequently asked questions

What are the key interrupting ratings for 3VA2510-5HN32-0JH0?

187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V. These are the maximum fault currents the breaker can safely interrupt at those voltages.

What is the rated continuous current of this MCCB?

1000 A at 40 °C through 55 °C ambient, with thermal derating above that: 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C.

Where can I buy 3VA2510-5HN32-0JH0 and how is it quoted?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — figures are confirmed at quote time, not listed here.

MPN
3VA2510-5HN32-0JH0