Skip to main content
Siemens 3VA2510-5HN32-0KB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HN32-0KB0 SENTRON MCCB, 1000 A, 187 kA at 2

MPN3VA2510-5HN32-0KB0

Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 1000 A, ETU350 release, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2510-5HN32-0KB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2510-5HN32-0KB0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W

Protection & Trip Unit

3VA2510-5HN32-0KB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI

Construction & Connection

3VA2510-5HN32-0KB0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2510-5HN32-0KB0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo

Environmental

3VA2510-5HN32-0KB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2510-5HN32-0KB0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

What this MCCB delivers

The Siemens 3VA2510-5HN32-0KB0 is a SENTRON 3VA2 molded case circuit breaker rated for line protection — 3-pole, 1000 A continuous current (Iu) with an ETU350 electronic trip unit. The interrupting capacity climbs to 187 kA at 240 V, 121 kA at 415 V, and still holds 53 kA at 690 V, which covers most industrial distribution panels and motor control centers without needing a current-limiting fuse upstream. The ETU350 release gives you adjustable long-time (tr) from 0.5 to 17 s and short-time (tsd) from 0.04 to 0.4 s, plus an instantaneous pickup fixed at 10 000 A. That range lets you coordinate selectively with downstream breakers — the short-time delay keeps the main from tripping on a branch fault, which is the difference between a localized outage and a whole-panel blackout.

Continuous current and thermal derating

The breaker carries its full 1 000 A continuously up to 55 °C ambient. At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. If your panel runs hot — say a non-ventilated enclosure near a furnace line — that derating curve tells you exactly where you lose headroom. The maximum operating temperature is 70 °C; storage range is -40 to 80 °C. Power loss at full load is 123 W. That's not trivial in a sealed enclosure — factor it into your thermal budget if you're grouping several breakers on a bus.

Physical fit and mounting

Dimensions are 320 mm high, 210 mm wide, 120 mm deep. The 210 mm width is a standard 8.3-inch footprint for this frame size — it bolts into a panel cutout designed for SENTRON 3VA2 breakers, no adapter plate needed. Front IP40 rating means it's protected against tools and wires but not washdown; keep it inside a clean enclosure.

Frequently asked questions

Where can I buy 3VA2510-5HN32-0KB0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the interrupting ratings at different voltages?

At 240 V it interrupts 187 kA, at 415 V it interrupts 121 kA, and at 690 V it interrupts 53 kA.

What is the continuous current rating and how does it derate with temperature?

Rated continuous current is 1 000 A up to 55 °C. At 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A.

Does this breaker have communication or ground-fault monitoring?

No — the listing shows no communication function and no ground-fault monitoring version. It is a straight line-protection breaker with the ETU350 trip unit.

MPN
3VA2510-5HN32-0KB0