Siemens 3VA2510-5HN32-0KE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5HN32-0KE0 Circuit Breaker, 1000A, 55kA @ 41

MPN3VA2510-5HN32-0KE0

Siemens 3VA2 IEC frame 1000, 3-pole circuit breaker, 55kA breaking capacity class M @ 415V, ETU350 LSI electronic trip unit, In=1000A, with shunt trip left and 4 auxiliary contacts.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

What this 3VA2 breaker delivers

The Siemens 3VA2510-5HN32-0KE0 is a 3-pole IEC frame 1000 circuit breaker with a 55 kA breaking capacity at 415 V (class M), meaning it can safely interrupt fault currents up to that level without upstream cascading — a key selectivity consideration for main or feeder breakers in a distribution panel. It carries the ETU350 LSI electronic trip unit, adjustable: overload protection Ir from 400 A to 1000 A, short-time pickup Isd from 1.5 to 10 x Ir, and instantaneous pickup Ii fixed at 10 x In. That range lets the site electrical engineer coordinate downstream devices while keeping the main breaker selective. The shunt trip (left-mounted, 208–277 V AC 50/60 Hz or 220–250 V DC) and four auxiliary contacts are factory-integrated — no field-assembly of accessories needed. For a commissioning engineer, that means one order code, one nameplate to verify against the PO.

Panel integration notes

Mounts in a standard IEC distribution panel — frame 1000 footprint. The nut keeper kit (included per the description) secures the breaker to the mounting plate without loose hardware, which speeds panel assembly and avoids dropped fasteners in live gear. Shunt trip wired left-side; verify control voltage matches the listed dual-range coil (208–277 V AC or 220–250 V DC). Auxiliary contacts (4 AUX) provide status feedback to the PLC or safety circuit — common for pump or conveyor feeder breakers where remote trip indication is required.

Frequently asked questions

What are the key ratings of 3VA2510-5HN32-0KE0?

IEC frame 1000, 3-pole, 55 kA breaking capacity at 415 V (class M), ETU350 LSI electronic trip, In=1000 A, Ir adjustable 400–1000 A, Isd 1.5–10 x Ir, Ii=10 x In, with shunt trip (208–277 V AC / 220–250 V DC) and 4 auxiliary contacts.

MPN
3VA2510-5HN32-0KE0