Skip to main content
Siemens 3VA2510-5JP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5JP42-0AA0 SENTRON MCCB, 1000 A, 4-Pole, ETU

MPN3VA2510-5JP42-0AA0
Active

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2510-5JP42-0AA0, 1000 A, 4-pole, ETU550 electronic trip unit, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2510-5JP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5JP42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.330 W
3VA2510-5JP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2510-5JP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5JP42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA2510-5JP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5JP42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11.02 in
Depth (in)4.72 in

Product details

The Siemens SENTRON 3VA2510-5JP42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 1000 A continuous current at 40 °C, with no derating needed up to 55 °C — it holds the full 1000 A through that range, then steps down to 955 A at 60 °C and 815 A at 70 °C. That thermal profile means it handles full-rated load in most ventilated enclosures without forced cooling. The ETU550 electronic trip unit gives adjustable long-time, short-time, and instantaneous protection, plus ground-fault detection is not built in (this version ships without). Breaking capacity hits 187 kA at 240 V, 121 kA at 415/440 V, and still clears 52.5 kA at 690 V — enough for high-fault utility feeds or transformer secondaries.

Sizing and deployment

At 280 mm wide × 320 mm tall × 120 mm deep, this breaker is a panel-mount unit — it bolts into a switchboard or distribution panel via the rear mounting plate, not a DIN rail. Communication function is present via the COM module slot for BMS or SCADA reporting.

Frequently asked questions

What trip unit does this MCCB use?

It uses the ETU550 electronic trip unit, which provides adjustable long-time, short-time, and instantaneous protection curves. This version does not include ground-fault monitoring.

MPN
3VA2510-5JP42-0AA0