Skip to main content
Siemens 3VA2510-5KQ32-0AG0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5KQ32-0AG0 SENTRON MCCB, 1000 A, 187 kA at 2

MPN3VA2510-5KQ32-0AG0

Siemens SENTRON 3VA2, Molded case circuit breaker, 3-pole, 1000 A, 187 kA at 240 V, 121 kA at 415 V, 53 kA at 690 V, ETU860 release, line protection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5KQ32-0AG0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5KQ32-0AG0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5KQ32-0AG0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-5KQ32-0AG0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5KQ32-0AG0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2510-5KQ32-0AG0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5KQ32-0AG0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

MCCB for high-fault plant feeders

The ETU860 electronic trip unit gives you adjustable long-time (tr 0.5–25 s) and short-time (tsd 0.05–0.5 s) delay settings, so coordination with downstream breakers is tunable, not fixed. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that put this squarely in high-fault-current plant feeders or transformer secondaries where the available fault current is well above typical 25–65 kA MCCB ratings.

Full 1000 A holds through 55 °C ambient; at 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. That's a shallow curve — you lose 18.5 % by 70 °C, not the steeper drop some frames show — so a warm enclosure (say 50–55 °C) still delivers the nameplate current. Max power loss is 123 W, which factors into enclosure cooling calcs. Dimensions: 210 mm wide, 320 mm high, 120 mm deep. Front IP40.

Communication and monitoring

ETU860 release supports communication function and other measurement function. Ground fault monitoring uses summation current formation on L-conductor. Latching endurance is 10 000 cycles mechanical.

MPN
3VA2510-5KQ32-0AG0