Skip to main content
Siemens 3VA2510-5KQ32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5KQ32-0BH0 SENTRON MCCB, 1000 A, 187 kA

MPN3VA2510-5KQ32-0BH0

Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 1000 A, ETU860, 187 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5KQ32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5KQ32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5KQ32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-5KQ32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5KQ32-0BH0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2510-5KQ32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5KQ32-0BH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens 3VA2510-5KQ32-0BH0 is a SENTRON 3VA2 molded case circuit breaker, 3-pole, rated for 1000 A continuous current with an ETU860 electronic trip unit. It's a line-protection breaker — meaning it's sized for main feeder or large distribution duty, not motor branch circuit protection. The interrupting ratings are 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V, so it handles high-fault utility feeds without cascading upstream.

At 60 °C it drops to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. The ETU860 trip unit gives you adjustable long-time pickup (Ir) from 0.5 to 1.0 × In, so you can set the 1000 A frame down to 500 A for a smaller feeder without swapping breakers. Short-time delay (tsd) is adjustable from 0.05 to 0.5 s — useful for selective coordination downstream. Power loss hits 123 W at rated current. That's heat that stays in the enclosure, so factor it into your thermal budget — especially if you're packing multiple breakers in a single panel.

Dimensions are 210 mm wide, 320 mm high, 120 mm deep.

Frequently asked questions

Where can I buy 3VA2510-5KQ32-0BH0 and get a price?

This part is sourced to order against an RFQ through independent distribution channels. Submit a request for quote — availability and current pricing are confirmed at quote time, not from a static listing.

What is the interrupting rating of 3VA2510-5KQ32-0BH0 at 415 V?

121 kA at 415 V. That's the short-circuit breaking capacity at that voltage level — sufficient for most industrial main switchboards with high fault current.

What compliance documentation does this brand provide for 3VA2510-5KQ32-0BH0?

As a SENTRON 3VA2 series MCCB, it carries IEC/EN 60947-2 certification. Standard documentation includes the declaration of conformity, CE marking, and RoHS/REACH compliance statements from Siemens.

MPN
3VA2510-5KQ32-0BH0