Skip to main content
Siemens 3VA2510-5KQ32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5KQ32-0CH0 SENTRON MCCB, 1000 A, 187 kA

MPN3VA2510-5KQ32-0CH0

Siemens SENTRON 3VA2510-5KQ32-0CH0, molded case circuit breaker, 3-pole, 1000 A rated continuous current, 187 kA at 240 V, ETU860 electronic trip unit, line protection, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA2510-5KQ32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5KQ32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5KQ32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-5KQ32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5KQ32-0CH0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2510-5KQ32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5KQ32-0CH0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

The Siemens SENTRON 3VA2510-5KQ32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 1000 A continuous current at 40 °C, with the same rating holding flat through 55 °C — a thermal plateau that avoids derating in most ventilated enclosures. Above 55 °C it derates linearly to 815 A at 70 °C, so the ambient inside the panel governs the actual continuous current you can carry. The interrupting ratings are 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V, which means it can clear faults up to those levels without upstream cascading — critical for high-fault utility feeds or transformer secondaries. The ETU860 electronic trip unit provides adjustable long-time (tr 0.5–25 s) and short-time (tsd 0.05–0.5 s) delay settings, plus ground-fault monitoring via summation current formation on the L-conductor.

The breaker measures 320 mm high by 210 mm wide by 120 mm deep — a footprint that fits standard panel cutouts for 1000 A frame MCCBs. Communication function is built in, so it can integrate with a BMS or SCADA system for remote trip indication and metering.

Frequently asked questions

Where can I buy 3VA2510-5KQ32-0CH0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time estimate.

What is the closest functional second-source to 3VA2510-5KQ32-0CH0?

The peer order codes 5SQ2370-2YA05, 5SQ2370-2YA04, and 5SQ2370-2YA01 are listed as alternate MPNs. Whether they drop into the same panel without rewiring depends on the specific mounting footprint and terminal arrangement — verify the physical dimensions and connection scheme before substituting.

MPN
3VA2510-5KQ32-0CH0