The 1000 A rating holds up to 55 °C ambient; above that it derates to 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C, so if your panel runs hot, factor that in.
The breaker measures 210 mm wide, 320 mm high, and 120 mm deep. The ETU860 trip unit is programmable via the communication function (yes, it has one), so you can set the long-time pickup Ir from 0.5 to 1.0 × Iu (500 to 1000 A) and the short-time delay tsd from 0.05 to 0.5 s.