Skip to main content
Siemens 3VA2510-5KQ32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5KQ32-0JA0 SENTRON MCCB, 1000 A, 3-pole, ETU

MPN3VA2510-5KQ32-0JA0

Siemens SENTRON 3VA2510-5KQ32-0JA0, Molded case circuit breaker, 3-pole, 1000 A, ETU860 electronic trip unit, line protection, 187 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5KQ32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5KQ32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5KQ32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-5KQ32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5KQ32-0JA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2510-5KQ32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5KQ32-0JA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

Line protection MCCB with ETU860 — 1000 A continuous, 187 kA interrupting

The Siemens SENTRON 3VA2510-5KQ32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 1000 A continuous current at 40 °C, with an interrupting capacity of 187 kA at 240 V AC, 121 kA at 415 V, and 53 kA at 690 V. It carries an ETU860 electronic trip unit — fully adjustable for long-time (tr 0.5–25 s), short-time (tsd 0.05–0.5 s), and instantaneous protection, with Ir adjustable up to 1000 A. Rated for line protection (not motor-only), this MCCB delivers full-genealogy traceability through the SENTRON platform — the ETU860 logs event data and supports communication functions, enabling integration with higher-level monitoring systems for predictive maintenance and fault analysis.

At 60 °C ambient the breaker carries 955 A; at 70 °C it derates to 815 A. Maximum power loss is 123 W. Panel builders should account for this heat dissipation when calculating enclosure ventilation and busbar ampacity — the 120 mm depth and 210 mm width fit standard MCCB mounting footprints, but adjacent devices must be spaced per Siemens derating guidelines to avoid nuisance tripping.

Frequently asked questions

Where can I buy 3VA2510-5KQ32-0JA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead times are published here.

What are the key ratings of 3VA2510-5KQ32-0JA0?

Rated continuous current 1000 A at 40 °C, interrupting capacity 187 kA at 240 V / 121 kA at 415 V / 53 kA at 690 V, 3-pole, ETU860 electronic trip unit with adjustable long-time, short-time, and instantaneous protection. Rated insulation voltage 800 V, IP40 front protection.

Will 3VA2510-5KQ32-0JA0 drop into a panel specified for 3VA1110-5EE32-0JA0?

The 3VA2510-5KQ32-0JA0 is a physically larger frame (210 mm wide, 320 mm tall, 120 mm deep) than the 3VA1110 series. It will not fit the same cutout or busbar spacing without panel rework. The 3VA1110 is a lower-current, smaller-frame MCCB; the 3VA2510 is a 1000 A class feeder breaker.

MPN