Skip to main content
Siemens 3VA2510-5KQ32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-5KQ32-0JC0 SENTRON MCCB, 1000 A, 3-pole, ETU

MPN3VA2510-5KQ32-0JC0

Siemens SENTRON 3VA2510-5KQ32-0JC0, Molded case circuit breaker, 3-pole, 1000 A, ETU860 electronic trip unit, line protection, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-5KQ32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-5KQ32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 690 V53 kA
Power loss, max.123 W
3VA2510-5KQ32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-5KQ32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-5KQ32-0JC0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
3VA2510-5KQ32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-5KQ32-0JC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

Siemens 3VA2510-5KQ32-0JC0 — 1000 A SENTRON MCCB with ETU860

Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 53 kA at 690 V — numbers that govern its fault-clearing capability in a distribution panel. The ETU860 allows adjustable long-time (tr) and short-time (tsd) delay settings, with tr from 0.5 to 25 seconds and tsd from 0.05 to 0.5 seconds, giving selectivity coordination flexibility downstream.

Derating begins at 60 °C (955 A), dropping to 885 A at 65 °C and 815 A at 70 °C. The enclosure footprint is 210 mm wide, 320 mm high, and 120 mm deep — dimensions that determine backpanel layout and whether it fits existing busbar or cable-connection zones.

What the ETU860 release means for coordination

The ETU860 is a microprocessor-based trip unit that supports adjustable long-time pickup (Ir) from 0.4× to 1.0× Iu — here up to 1000 A — plus short-time and instantaneous settings. Ground-fault monitoring is via summation current formation on the line conductor. Maximum power loss is 123 W, a number to factor into enclosure thermal calculations when the breaker is enclosed with other heat sources.

Frequently asked questions

What is 3VA2510-5KQ32-0JC0's listed depth?

The depth is 120 mm. Combined with a width of 210 mm and height of 320 mm, this defines the panel cutout and backpanel clearance needed.

MPN
3VA2510-5KQ32-0JC0