Skip to main content
Siemens 3VA2510-6HK32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2510-6HK32-0AA0 MCCB, 1000 A, 242 kA at 2

MPN3VA2510-6HK32-0AA0
Active

Siemens SENTRON, molded case circuit breaker, 3VA2510-6HK32-0AA0, 3-pole, 1000 A rated continuous current, 242 kA interrupting at 240 V, ETU340 electronic trip unit, line protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2510-6HK32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-6HK32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V74 kA
Power loss, max.330 W
3VA2510-6HK32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
3VA2510-6HK32-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-6HK32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Auxiliary CO contacts0
3VA2510-6HK32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-6HK32-0AA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in
Depth (in)4.7 in

Product details

The Siemens SENTRON 3VA2510-6HK32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 1000 A at 40 °C ambient and an insulation voltage Ui of 800 V.

Thermal derating and trip unit

Full 1000 A rating holds through 55 °C; at 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. The ETU340 electronic overcurrent release is adjustable for Ir and tr — Ir maxes at 1000 A with a fixed tr of 1300 ms, meaning the long-time pickup and delay are set for coordination with downstream devices. Power loss maxes at 330 W, so panel ventilation matters at full load.

Dimensions: 320 mm high, 210 mm wide, 120 mm deep — fits standard MCCB panel cutouts. Front protection is IP40, suitable for enclosed switchboards; storage range -40 °C to 80 °C, operating -25 °C to 70 °C.

Frequently asked questions

Where can I buy 3VA2510-6HK32-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is 3VA2510-6HK32-0AA0's interrupting capacity at 240 V?

242 kA at 240 V, with 187 kA at 415 V and 440 V, 121 kA at 500 V, and 74 kA at 690 V.

What is the rated continuous current of 3VA2510-6HK32-0AA0?

1000 A at 40 °C through 55 °C, derating to 955 A at 60 °C, 885 A at 65 °C, and 815 A at 70 °C.

MPN
3VA2510-6HK32-0AA0