Skip to main content
Siemens 3VA2510-6HN32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-6HN32-0AC0 SENTRON MCCB, 1000 A, 3-Pole, Lin

MPN3VA2510-6HN32-0AC0

Siemens SENTRON 3VA2510-6HN32-0AC0, molded case circuit breaker, 3-pole, line protection, rated continuous current 1000 A, ETU350 electronic trip unit, interrupting ratings 242 kA at 240 V / 187 kA at 415 V / 74 kA at 690 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-6HN32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-6HN32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.123 W
3VA2510-6HN32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2510-6HN32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-6HN32-0AC0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-6HN32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-6HN32-0AC0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

MCCB for high-current line protection

The Siemens SENTRON 3VA2510-6HN32-0AC0 is a 3-pole molded case circuit breaker rated for a continuous current Iu of 1 000 A, fitted with an ETU350 electronic trip unit for line protection duty. It carries interrupting ratings of 242 kA at 240 V, 187 kA at 415 V, and 74 kA at 690 V — figures that define its fault-clearing capability at each voltage level, not just the highest number. The trip unit offers adjustable long-time pickup Ir up to 1 000 A, instantaneous pickup Ii up to 10 000 A, and short-time delay tsd from 0.04 s to 0.4 s, giving the specifying engineer control over coordination with downstream devices.

The breaker carries its full 1 000 A continuously from 40 °C up to 55 °C ambient; at 60 °C it derates to 955 A, at 65 °C to 885 A, and at 70 °C to 815 A. That means a panel designer who expects a 40 °C internal ambient can size the bus and enclosure for the full rating, while a high-temp installation (e.g., near a furnace line) must account for the drop. Physical dimensions are 210 mm wide, 320 mm high, and 120 mm deep — a standard footprint for this frame class, mountable on a backplate or in a switchboard enclosure. IP40 on the front face keeps out tools and fingers but is not rated for washdown; keep it indoors or behind a sealed door.

Frequently asked questions

Where can I buy 3VA2510-6HN32-0AC0?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the interrupting ratings at different voltages?

At 240 V it interrupts 242 kA, at 415 V it interrupts 187 kA, and at 690 V it interrupts 74 kA. These are the certified values for this specific breaker.

What trip unit does this MCCB use?

It uses the ETU350 electronic trip unit with adjustable long-time pickup Ir up to 1 000 A, instantaneous pickup Ii up to 10 000 A, and short-time delay tsd adjustable from 0.04 s to 0.4 s.

MPN
3VA2510-6HN32-0AC0