Skip to main content
Siemens 3VA2510-6HN32-0BL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-6HN32-0BL0 SENTRON MCCB, 1000 A, 242 kA

MPN3VA2510-6HN32-0BL0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2510-6HN32-0BL0, 3-pole, 1000 A rated continuous current, 242 kA breaking capacity at 240 V, ETU350 electronic trip unit, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2510-6HN32-0BL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-6HN32-0BL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 690 V74 kA
Power loss, max.123 W
3VA2510-6HN32-0BL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2510-6HN32-0BL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-6HN32-0BL0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
3VA2510-6HN32-0BL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-6HN32-0BL0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in

Product details

What this 1000 A MCCB delivers

The Siemens SENTRON 3VA2510-6HN32-0BL0 is a 3-pole molded case circuit breaker rated for 1000 A continuous current (Iu) with a breaking capacity of 242 kA at 240 V AC — enough to handle high-fault utility feeds or large transformer secondaries without cascading upstream. The ETU350 electronic trip unit gives you adjustable long-time (Ir 0.5–1.0× Iu, tr 0.5–17 s) and short-time (Isd, tsd 0.04–0.4 s) protection curves, plus a fixed instantaneous pickup at 10× Iu (li 10000 A). That means you can coordinate selectively with downstream feeders and still clear a bolted fault fast.

Panel fit and thermal derating

The breaker measures 210 mm wide × 320 mm high × 120 mm deep — a standard 3-pole MCCB footprint for a 1000 A frame. It carries its full 1000 A rating up to 55 °C ambient; at 60 °C you derate to 955 A, at 70 °C to 815 A. Mounting is via four screws on the rear flange — no DIN-rail clip on this frame size.

That means you can BOM it for new designs and hold it as a critical spare without worrying about a sudden EOL. For pricing and availability, submit an RFQ; we source this through Siemens distribution and independent channels, confirmed at quote time.

MPN
3VA2510-6HN32-0BL0