Skip to main content
Siemens 3VA2510-6JP42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-6JP42-0AA0 SENTRON MCCB, 1000A, 4P, ETU550

MPN3VA2510-6JP42-0AA0
Active

Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2510-6JP42-0AA0, 1000 A rated current, 4-pole, ETU550 electronic trip unit, 242 kA breaking capacity at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2510-6JP42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-6JP42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V73.5 kA
Power loss, max.330 W
3VA2510-6JP42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
3VA2510-6JP42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-6JP42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA2510-6JP42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-6JP42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.10 000
Height320 mm
Width280 mm
Depth120 mm
Height (in)12.6 in
Width (in)11.02 in
Depth (in)4.72 in

Product details

The Siemens SENTRON 3VA2510-6JP42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 1000 A at 40 °C ambient, with no derating required up to 55 °C — the full 1000 A holds across that band. At 60 °C the rating steps to 955 A, then 885 A at 65 °C, and 815 A at 70 °C, per the published thermal curve. Breaking capacity is specified across five voltage points: 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 73.5 kA at 690 V. Maximum power loss is 330 W.

Dimensions are 320 mm height, 280 mm width, and 120 mm depth. The 280 mm width is the critical panel cutout dimension — verify against existing busbar or mounting footprint before committing the gland plate layout.

Frequently asked questions

Where can I buy 3VA2510-6JP42-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is 3VA2510-6JP42-0AA0's listed depth?

The depth is 120 mm (4.72 in).

What is 3VA2510-6JP42-0AA0's listed width?

The width is 280 mm (11.02 in).

What compliance documentation does Siemens provide for 3VA2510-6JP42-0AA0?

As a SENTRON series MCCB, this breaker is designed to meet IEC 60947-2 and UL 489 standards. Specific declarations (RoHS, REACH, CE, UKCA, EAC) are typically included in the manufacturer's documentation package available on request.

MPN
3VA2510-6JP42-0AA0