Skip to main content
Siemens 3VA2510-7KQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2510-7KQ32-0AA0 SENTRON MCCB, 1000 A, 440 kA at 2

MPN3VA2510-7KQ32-0AA0
Active

Siemens SENTRON 3VA2510-7KQ32-0AA0, molded case circuit breaker, line protection, 3-pole, 1000 A rated continuous current, 440 kA at 240 V, ETU860 electronic trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2510-7KQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2510-7KQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C1 000 A
Current at 45 °C1 000 A
Current at 50 °C1 000 A
Current at 55 °C1 000 A
Current at 60 °C955 A
Current at 65 °C885 A
Current at 70 °C815 A
Switching capacity classC
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 690 V74 kA
Power loss, max.123 W
3VA2510-7KQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
3VA2510-7KQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2510-7KQ32-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionYes
Auxiliary CO contacts0
3VA2510-7KQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2510-7KQ32-0AA0 — Mechanical
ParameterValue
Height320 mm
Width210 mm
Depth120 mm
Height (in)12.6 in
Width (in)8.3 in
Depth (in)4.7 in

Product details

The Siemens 3VA2510-7KQ32-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 1000 A continuous current, holding that rating from 40 °C through 55 °C ambient before derating starts — 955 A at 60 °C, 885 A at 65 °C, 815 A at 70 °C. The 3-pole line-protection version carries an ETU860 electronic trip unit with adjustable long-time pickup (Ir) from 0.5 to 1.0× In (500–1000 A) and short-time delay (tsd) adjustable 0.05–0.5 s — so you can shape the curve for selective coordination downstream without nuisance trips. Breaking capacity is the headline: 440 kA at 240 V AC, 242 kA at 415 V, 74 kA at 690 V. At 415 V the 242 kA still covers virtually all industrial service-entrance applications.

Panel integration and communication

Dimensions: 320 mm height, 210 mm width, 120 mm depth. That depth (120 mm) is compact for a 1000 A MCCB — it fits standard 400 mm deep enclosures without the door interfering. The breaker supports communication functions (the ETU860 trip unit can interface with fieldbus or Modbus via an optional communication module), so it can report trip events, current draw, and status to a PLC or SCADA — useful for predictive maintenance and remote monitoring in larger plants.

Frequently asked questions

What is the breaking capacity of 3VA2510-7KQ32-0AA0 at 415 V?

242 kA at 415 V AC. This is high enough for most industrial service-entrance and distribution applications.

What overcurrent release does this MCCB use?

It uses the ETU860 electronic trip unit, adjustable from 500 A to 1000 A (Ir), with short-time delay 0.05–0.5 s.

Where can I buy 3VA2510-7KQ32-0AA0?

It is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability.

MPN
3VA2510-7KQ32-0AA0